Quantcast
Total 205 results | Page 1 of 11
Fire Test

GA ASW 1000

Steel Stud (Non-load-bearing)
Area Seperation Wall
Fire Rating

2 hr.

STC

N/A

Thickness (in.)

3-1/2"

Suitable for attic space.

  • Air Space - air space layer
  • Steel Studs - "H" shaped studs, 2 in. wide by 1-3/8 in. deep, min. 25 ga. steel spaced max. @ 24 in
  • Gypsum Board - Two layers of 1 in. thick by nom. 2 ft. wide gypsum liner panels inserted in H studs - SHEETROCK Brand Gypsum Liner Panel
  • Air Space - air space layer

Visit U336

Fire Test

GA-WP-8131

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

5-1/8"

  • Cement Board - 1/2 in. thick board, applied horizontally or vertically - DUROCK Brand Cement Board Next Gen
  • Sheathing Materials - Min. 15/32 in. thick, 4 ft. wide, wood structural panels, min. grade "sheathing" applied vertically
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3 in. mineral wool batt insulation
  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK® UltraLight Firecode X Gypsum Panels

Visit U303

Fire Test

UL U301

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

2 hr.

STC

N/A

Thickness (in.)

6"

Visit U301

Fire Test

UL U302

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

2 hr.

STC

N/A

Thickness (in.)

10-3/4"

  • Gypsum Board - Two layers of 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK Brand FIRECODE Core (Type X)
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Gypsum Sheathing (non-rated) - 1/2 in. gypsum sheathing (non-rated) applied horizontally
  • Corrugated Wall Ties - 3/4 in. wide by 6-5/8 in. long, 20 MSG galv steel. Attached to each stud with 2-3/8 in. long 8d cement coated nails, every sixth course of bricks
  • Clay Face Bricks - 2-1/4 in. x 3-3/4 in. x 8 in. with cored holes, laid in full bed of mortar 3/8 to 1/2 in. thick consisting of three parts of clean sharp sand to one part of portland cement (proportioned by vol) and 15 percent hydrated lime (by cement vol)

Visit U302

Fire Test

UL U303

Wood Stud (Load-bearing)
Interior Partitions
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

5-1/8"

  • Cement Board - 1/2 in. cement board applied vertical or horizontal - DUROCK Brand Cement Board Next Gen
  • Sheathing Materials - Min. 15/32 in. thick, 4 ft. wide, wood structural panels, min. grade "sheathing" applied vertically
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3 in. mineral wool batt insulation
  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK Brand UltraLight Firecode X Gypsum Panels

Visit U303

Fire Test

UL U305

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: RAL-TL11-172
Fire Rating

1 hr.

STC

33

Thickness (in.)

4-3/4"

Visit U305

Fire Test

UL U305

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: RAL-TL11-130 / RAL-TL11-173
Fire Rating

1 hr.

STC

34

Thickness (in.)

4-3/4"

Visit U305

Fire Test

UL U305

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

4-3/4"

Visit U305

Fire Test

UL U305

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: USG-860807
Fire Rating

1 hr.

STC

37

Thickness (in.)

4-3/4"

Visit U305

Fire Test

UL U305

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: RAL-TL11-129 / RAL-TL15-048
Fire Rating

1 hr.

STC

32

Thickness (in.)

4-3/4"

Visit U305

Fire Test

UL U308

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

2 hr.

STC

N/A

Thickness (in.)

6"

Visit U308

Fire Test

UL U311

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: SA-830702
Fire Rating

1 hr.

STC

52

Thickness (in.)

5-1/4"

Visit U311

Fire Test

UL U314

Wood Stud (Load-bearing)
Interior Partitions
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

4-3/4"

Visit U314

Fire Test

UL U317

Wood Stud (Load-bearing)
Interior Partitions
Fire Rating

0.75 hr.

STC

N/A

Thickness (in.)

4-1/2"

Visit U317

Fire Test

UL U327

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

5-1/4"

Visit U327

Fire Test

UL U327

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: RAL-TL11-083
Fire Rating

1 hr.

STC

48

Thickness (in.)

5-1/4"

  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK Brand FIRECODE Core (Type X)
  • Resilient Channel - 1/2 in. resilient channel or equivalent one side
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3-1/2 in. fiberglass wool insulation
  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK Brand FIRECODE Core (Type X)

Visit U327

Fire Test

UL U327

Wood Studs
Interior Partitions
Sound Test: RAL-TL11-082
Fire Rating

1 hr.

STC

46

Thickness (in.)

5-1/4"

  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK® UltraLight Firecode X Gypsum Panels
  • Resilient Channel - 1/2 in. deep resilient furring channels, min. 25 ga. corrosion-protected steel, spaced vertically a max. of 24 in. OC
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3-1/2 in. fiberglass insulation friction fit in stud spaces
  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK® UltraLight Firecode X Gypsum Panels
Fire Test

UL U329

Wood Stud (Load-bearing)
Exterior Walls
Fire Rating

1 hr.

STC

N/A

Thickness (in.)

4-7/8"

  • Gypsum Board - 5/8 in. thick gypsum sheathing applied horizontally or vertically - SECUROCK Brand Glass-Mat Sheathing FIRECODE Core - 5/8 in.
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3-1/2 in. mineral wool batt insulation
  • Cement Board - 1/2 in. thick board, applied horizontally or vertically. - DUROCK Brand Cement Board Next Gen
  • Bond Coat for Setting Tile - Latex modified portland cement mortar or .1 type I organic adhesive applied with a notched trowel
  • Ceramic Tile - 1/4 in. thick ceramic tile, joints filled with grout.

Visit U329

Fire Test

UL U329 or GA-WP-3441

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: USG-840404
Fire Rating

1 hr.

STC

37

Thickness (in.)

5"

  • Ceramic Tile - 1/4 in. thick ceramic tile, joints filled with grout.
  • Cement Board - 1/2 or 5/8 in. thick board, applied horizontally or vertically - DUROCK Brand Cement Board Next Gen
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3-1/2 in. mineral wool batt insulation
  • Cement Board - 1/2 or 5/8 in. thick board, applied horizontally or vertically - DUROCK Brand Cement Board Next Gen
  • Ceramic Tile - 1/4 in. thick ceramic tile, joints filled with grout.

Visit U329

Fire Test

UL U329 or GA-WP-3441

Wood Stud (Load-bearing)
Interior Partitions
Sound Test: USG-840314
Fire Rating

1 hr.

STC

40

Thickness (in.)

4-7/8"

  • Gypsum Board - 5/8 in. thick gypsum board applied horizontally or vertically. - SHEETROCK Brand FIRECODE Core (Type X)
  • Wood Studs - 2 in. x 4 in. wood studs spaced max. 16 in. OC
  • Batts and Blankets - 3-1/2 in. mineral wool batt insulation
  • Cement Board - 1/2 thick board, applied horizontally or vertically - DUROCK Brand Cement Board Next Gen
  • Bond Coat for Setting Tile - Latex modified portland cement mortar or .1 type I organic adhesive applied with a notched trowel
  • Ceramic Tile - 1/4 in. thick ceramic tile, joints filled with grout.

Visit U329

Disclaimer: Most of the published USG sound tests in Design Studio are performed in a laboratory environment. Every detail in the construction of these assemblies is critical in order to achieve the best possible result. When you go from a laboratory to the real world, there are variables that affect the movement of sound that cannot be reproduced in a laboratory. For this reason, we recommend consulting with a local acoustician to insure the highest level of performance for sound transmission.