Quantcast
Total 195 results | Page 2 of 6
Fire Test

UL G556

Fire Rating

1 hour

STC

N/A

Featured

Assembly Description
  • Floor Substrate - Concrete structural panel subfloor
  • Structural Members - Min. 10 in. (254 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design G556

Fire Test

UL G556 or GA-FC-1800

Fire Rating

2 hour

STC

N/A

Featured

Assembly Description
  • Floor Underlayment - Min.1/2 in. (13 mm) thick gypsum-fiber board
  • Floor Substrate - Concrete structural panel subfloor
  • Structural Members - Min. 10 in. (254 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design G556

Fire Test

UL G556 or GA-FC-1800

Fire Rating

2 hour

STC

N/A

Featured

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Floor Substrate - Concrete structural panel subfloor
  • Structural Members - Min. 10 in. (254 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design G556

Fire Test

UL G557

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Concrete structural panel subfloor
  • Structural Members - Min. 10 in. (254 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - Two layers of 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design G557

Fire Test

UL G564

Fire Rating

2 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Carpet and pad
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G556

Fire Test

UL G564

Sound Test: RAL-OT05-13 & RAL-OT05-14
Fire Rating

2 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Vinyl plank
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Fire Rating

2 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Engineered hardwood
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Fire Rating

1 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Engineered hardwood
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Sound Test: RAL-OT05-15 & RAL-OT05-16
Fire Rating

1 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Carpet and pad
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Fire Rating

2 hour

STC

N/A

Featured

Assembly Description
  • Floor Underlayment - Min. 1 in. (25 mm) thick, min. compressive strength 3500 psi
  • Steel Deck - Min. 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - Min. 8 in. (203 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Batts and Blankets - Min. 3-1/2 in. (89 mm) thick mineral wool or fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Sound Test: RAL-OT05-09 & RAL-OT05-10
Fire Rating

1 hour

STC

60

Featured

Assembly Description
  • Floor Covering - Vinyl plank
  • Floor Underlayment - 1 in. (25 mm) thick, compressive strength 3500 psi
  • Sound Mat - 3/8 in. (10 mm) thick
  • Steel Deck - 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - 10 in. (254 mm) deep 16 ga. steel C-Joists 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced 12 in. (305 mm) OC
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL G564

Sound Test: RAL-OT05-11 & RAL-OT05-12
Fire Rating

1 hour

STC

63

Featured

Assembly Description
  • Floor Underlayment - Min. 1 in. (25 mm) thick, min. compressive strength 3500 psi
  • Steel Deck - Min. 9/16 in. (14 mm) deep 22 ga. corrugated steel deck
  • Structural Members - Min. 8 in. (203 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Batts and Blankets - Min. 3-1/2 in. (89 mm) thick mineral wool or fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - Gypsum board

Visit UL site for more info on Design G564

Fire Test

UL H505

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Concrete structural panel subfloor
  • Structural Members - Min. 8 in. (203 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board
Fire Test

UL J201

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Structural Members - Precast concrete
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 3/4 in. [508 x 1524 x 19]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 5/8 in. [508 x 1524 x 16]

Visit UL site for more info on Design J201

Fire Test

UL J504

Fire Rating

3 hour

STC

N/A

Assembly Description
  • Structural Members - 6 in. (152 mm) deep precast concrete
  • Ceiling Support - Furring channels spaced max. 24 in. (610 mm) OC
  • Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design J504

Fire Test

UL J924

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1/2 in. (13 mm) thick, min. compressive strength 1800 psi
  • Structural Members - 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J924

Fire Test

UL J924

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Structural Members - 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J924

Fire Test

UL J927

Fire Rating

30 mins.

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 6 in. (152 mm) deep precast concrete

Visit UL site for more info on Design J927

Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1/2 in. (13 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991

Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1 in. (25 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991

Fire Test

UL K504

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Ceiling Support - Suspension system
  • Gypsum Board - Three layers of 5/8 in. (16 mm) thick gypsum board
  • Ceiling Support - Furring channels spaced max. 16 in. (406 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design K504

Fire Test

UL K506

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Steel Strap - Min. 4 in. wide min 20 ga steel strap
  • Structural Members - Min. 6 in. (152 mm) deep 20 ga. steel c-joist spaced max. 24 in. (609 mm) OC
  • Gypsum Board - Three layers of 5/8 in. (16 mm) thick gypsum board
  • Ceiling Support - Furring channels spaced max. 16 in. (406 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design K506

Fire Test

UL L202

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Subfloor - 19/32 in. (15 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 3/4 in. [508 x 1524 x 19]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 5/8 in. [508 x 1524 x 16]
    • Panel Dimensions nom. in. - 24 in. by 60 in. x 3/4 in. [609 x 1524 x 19]
    • Panel Dimensions nom. in. - 24 in. by 60 in. x 5/8 in. [609 x 1524 x 16]

Visit UL site for more info on Design L202

Fire Test

UL L206

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design L206

Fire Test

UL L211

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Suspension system
  • Batts and Blankets - 6 in. (152 mm) thick fiberglass insulation
  • Gypsum Board - 1/2 in. (13 mm) thick gypsum board
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design L211

Fire Test

UL L212

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 19/32 in. (15 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design L212

Fire Test

UL L501

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Gypsum Board - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L501

Fire Test

UL L502

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 1/2 in.(13 mm) or 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L502

Fire Test

UL L508 or GA-FC-5310

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1-1/8 in. (29 mm) structural wood underlayment
  • Structural Members -Two, Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 48 in. (1219 mm) OC - null
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L508

Fire Test

UL L510

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1 in. (25 mm) by 6 in. (150 mm) tongue and groove lumber
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Gypsum Board - 1/2 in. (13 mm) thick gypsum board
  • Ceiling Support - Resilient channels spaced max. 24 in. (610 mm) OC
  • Finished Ceiling - 1/2 in. (13 mm) thick gypsum board

Visit UL site for more info on Design L510

Fire Test

UL L511 or GA-FC-5710

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1 in. (25 mm) by 6 in. (150 mm) tongue and groove lumber
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Gypsum Board - 5/8 in. (16 mm) thick gypsum board
  • Ceiling Support - Resilient channels spaced max. 24 in. (610 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L511

Fire Test

UL L512

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Gypsum Board - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L512

Fire Test

UL L514

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1 in. (25 mm) by 6 in. (150 mm) tongue and groove lumber
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Ceiling Support - Resilient channels spaced max. 24 in. (610 mm) OC
  • Finished Ceiling - 1/2 in.(13 mm) or 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L514

Fire Test

UL L515

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1 in. (25 mm) by 6 in. (150 mm) tongue and groove lumber
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Batts and Blankets - Mineral wool or fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC or suspension system
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L515

Fire Test

UL L516 or GA-FC-5115

Sound Test: USG-740703
Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 15/32 in. (12 mm) thick plywood underlayment
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Batts and Blankets - 3 in. thick fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 24 in. (610 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L516

Fire Test

UL L521 or GA-FC-5012

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 23/32 in. (18 mm) thick plywood underlayment
  • Structural Members - Min. 12 in. (305 mm) deep open web wood truss spaced max. 24 in. (609 mm) OC
  • Batts and Blankets - 3-1/2 in. (89 mm) thick mineral wool or fiberglass insulation
  • Ceiling Support - Resilient channels spaced max. 12 in. (305 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design L521