Fire Test

UL D209

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x2, 2x4
Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 20 ga. steel deck
  • Structural Members - Steel beam min. W10x21
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 1219 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design D209

Fire Test

UL D215

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x2, 2x4
Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 18 ga. steel deck
  • Structural Members - Steel beam min. W8x15
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]

Visit UL site for more info on Design D215

Fire Test

UL D218

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x15
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles (TYPE PSS, PSR, PSSP, PSRP, PAS, PAR, PASP, PARP, PIA, PII, PIIIA)
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16] (Optional metal pans to be used with acoustical ceiling)

Visit UL site for more info on Design D218

Fire Test

UL D218

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x4
Fire Rating

3 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 3 1/4 in. thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x15
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles (Type PSS, PSR, PSSP, PSRP)
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19] (Optional metal pans to be used with acoustical ceiling)

Visit UL site for more info on Design D218

Fire Test

UL D219

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x2, 2x4
Fire Rating

3 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 3-1/2 in. (89 mm) thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x15 or steel bar joists
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]

Visit UL site for more info on Design D219

Fire Test

UL D219

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x2, 2x4
Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x15 or steel bar joists
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design D219

Fire Test

UL D501

Fire Rating

1.5 hour

STC

N/A

Featured

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 3 in. (76 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x17
  • Ceiling Support - Suspension system
  • Finished Ceiling - 1/2 in. gypsum board

Visit UL site for more info on Design D501

Fire Test

UL D502

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 1-1/2 in. (38 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x28
  • Ceiling Support - Suspension system
  • Finished Ceiling - 5/8 in. (16 mm) gypsum board

Visit UL site for more info on Design D502

Fire Test

UL D503

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 2 in. (51 mm) deep 20 ga. steel deck
  • Structural Members - Steel beam min. W12x19
  • Ceiling Support - Suspension system
  • Finished Ceiling - 5/8 in. (16 mm) gypsum board

Visit UL site for more info on Design D503

Fire Test

UL J201

Fire Rating

2 hour

STC

N/A

Assembly Description
  • Structural Members - Precast concrete
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 609 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 3/4 in. [508 x 1524 x 19]
    • Panel Dimensions nom. in. - 20 in. by 60 in. x 5/8 in. [508 x 1524 x 16]

Visit UL site for more info on Design J201

Fire Test

UL J504

Fire Rating

3 hour

STC

N/A

Assembly Description
  • Structural Members - 6 in. (152 mm) deep precast concrete
  • Ceiling Support - Furring channels spaced max. 24 in. (610 mm) OC
  • Ceiling - 5/8 in. (16 mm) thick gypsum board

Visit UL site for more info on Design J504

Fire Test

UL J924

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Structural Members - 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J924

Fire Test

UL J924

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1/2 in. (13 mm) thick, min. compressive strength 1800 psi
  • Structural Members - 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J924

Fire Test

UL J927

Fire Rating

30 mins.

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 6 in. (152 mm) deep precast concrete

Visit UL site for more info on Design J927

Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1/2 in. (13 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991

Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1 in. (25 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991