Quantcast
Total 17 results | Page 1 of 1
Fire Test

UL D209

Concrete with Steel Floor Units and Beam Support
Panel Sizes: 2x2, 2x4
Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 20 ga. steel deck
  • Structural Members - Steel beam min. W10x21
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 3/4 in. [609 x 609 x 19]
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. [609 x 1219 x 16]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 3/4 in. [609 x 1219 x 19]
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. [609 x 1219 x 16]

Visit UL site for more info on Design D209

Fire Test

UL D501

Fire Rating

1.5 hour

STC

N/A

Featured

Assembly Description
  • Floor Substrate - Min. 2-1/2 in. (64 mm) thick concrete
  • Steel Deck - Min. 3 in. (76 mm) deep 22 ga. steel deck
  • Structural Members - Steel beam min. W8x17
  • Ceiling Support - Suspension system
  • Finished Ceiling - 1/2 in. gypsum board

Visit UL site for more info on Design D501

Fire Test

UL G502

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2 in. (50 mm) thick concrete
  • Steel Deck - Min. 9/16 in. (14 mm) deep 28 ga. corrugated steel deck
  • Structural Members - Steel bar joists spaced max. 24 in. (609 mm) OC
  • Ceiling Support - Furring channels spaced max. 24 in. (609 mm) OC
  • Finished Ceiling - 1/2 in. (13 mm) thick gypsum board

Visit UL site for more info on Design G502

Fire Test

UL G554

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Substrate - Min. 2 3/16 in. (56 mm) thick concrete
  • Steel Deck - Min. 1 5/16 in. (34 mm) deep 24 ga. corrugated steel deck
  • Structural Members - Steel bar joists spaced max. 54 in. (1372 mm) OC
  • Ceiling Support - Furring channels spaced max. 24 in. (609 mm) OC
  • Finished Ceiling - 5/8 in. (16 mm) thick gypsum board
Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1 in. (25 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991

Fire Test

UL J991

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 1/2 in. (13 mm) thick, min. compressive strength 1800 psi
  • Structural Members - Min. 8 in. (203 mm) deep precast concrete

Visit UL site for more info on Design J991

Fire Test

UL L510

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 1 in. (25 mm) by 6 in. (150 mm) tongue and groove lumber
  • Structural Members - Nom. 2 in. (51 mm) by 10 in. (254 mm) max. 16 in. (406 mm) OC
  • Gypsum Board - 1/2 in. (13 mm) thick gypsum board
  • Ceiling Support - Resilient channels spaced max. 24 in. (610 mm) OC
  • Finished Ceiling - 1/2 in. (13 mm) thick gypsum board

Visit UL site for more info on Design L510

Fire Test

UL L527

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Floor Underlayment - Min. 3/4 in. (19 mm) thick, min. compressive strength 1800 psi
  • Subfloor - 3/4 in. (19 mm) thick plywood underlayment
  • Structural Members - Min. 9 3/8 in. (238 mm) deep 16 ga. steel C-Joists max. 24 in. (610 mm) OC
  • Ceiling Support - Resilient channels spaced 16 in. OC
  • Finished Ceiling - Two layers 5/8 in. gypsum board

Visit UL site for more info on Design L527

Fire Test

UL P225

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.0 psf
  • Steel Deck - Min. 1 in. (25.4 mm) steel roof deck
  • Structural Member - Steel bar joist
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles

Visit UL site for more info on Design P225

Fire Test

UL P227

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.0 psf
  • Steel Deck - Min. 1 in. (25.4 mm) steel roof deck
  • Structural Member - Steel bar joist
  • Ceiling Support - Suspension system
  • Finished Ceiling - Acoustical ceiling tiles

Visit UL site for more info on Design P227

Fire Test

UL P230

Fire Rating

1.5 hour

STC

N/A

Featured

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.0 psf
  • Steel Deck - Min. 1-1/2 in. (38 mm) steel roof deck
  • Structural Member - Steel bar joist
  • Ceiling Support - Suspension system
  • Finished Ceiling - USG Paraline® Linear Metal Systems (I, II, III, and PLUS) or acoustical ceiling tiles
    • Panel Dimensions nom. in. - 24 in. by 24 in. by 5/8 in. (610 mm x 610 mm x 16 mm)
    • Panel Dimensions nom. in. - 24 in. by 48 in. by 5/8 in. (610 mm x 1219 mm x 16 mm) with M7 or MS125 wall angles

Visit UL site for more info on Design P230

Fire Test

UL P507

Fire Rating

1 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate - Gypsum concrete and gypsum form board
  • Gypsum Concrete - 500 psi
  • Gypsum Form Board - 1 in. (25.4 mm) thick gypsum panels
  • Structural Member - Steel bar joist
  • Ceiling Support - Suspension system
  • Finished Ceiling - 5/8 in. (15.9 mm) thick gypsum board

Visit UL site for more info on Design P507

Fire Test

UL P510

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick board 2.0 psf
  • Steel Deck - Min. 1 in. (25.4 mm) steel roof deck
  • Structural Member - Steel bar joist
  • Ceiling Support - Suspension system
  • Finished Ceiling - 5/8 in. (15.9 mm) thick gypsum board

Visit UL site for more info on Design P510

Fire Test

UL P718

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.2 psf
  • Steel Deck - Min. 1-1/2 in. (38 mm) steel roof deck
  • Structural Member - Steel beam or steel bar joist
  • Spray - Applied fire resistive material (Reference UL design for application requirements)

Visit UL site for more info on Design P718

Fire Test

UL P720

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.2 psf
  • Steel Deck - Min. 1-1/2 in. (38 mm) steel roof deck
  • Structural Member - Steel beam or steel bar joist
  • Spray - Applied fire resistive material (Reference UL design for application requirements)

Visit UL site for more info on Design P720

Fire Test

UL P728

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.2 psf
  • Steel Deck - Min. 1-1/2 in. (38 mm) steel roof deck
  • Structural Member - Steel beam or steel bar joist
  • Spray - Applied fire resistive material (Reference UL design for application requirements)

Visit UL site for more info on Design P728

Fire Test

UL P729

Fire Rating

1.5 hour

STC

N/A

Assembly Description
  • Roof Covering
  • Roof Substrate
  • Thermal Barrier: Gypsum Board - 5/8 in. (15.9 mm) thick gypsum board 2.2 psf
  • Steel Deck - Min. 1-1/2 in. (38 mm) steel roof deck
  • Structural Member - Steel beam or steel bar joist
  • Spray - Applied fire resistive material (Reference UL design for application requirements)

Visit UL site for more info on Design P729